Phase comparator
Product Features
This product is specifically designed and developed for indoor high-voltage live indicator panels (phase-testing terminals on the indicator panel). It is suitable for substations and distribution stations with multiple power supplies that utilize indoor high-voltage live indication devices operating at 3.6–40.5 kV and 50 Hz. During maintenance or before energizing, phase comparison can be performed at the low-voltage side without opening the switchgear doors.
Implementation Standard
GB25081
Product Usage
Voltage verification function: Insert the plug of the phase comparator into one of the phase sockets on the display unit (e.g., L1, L2, or L3), and connect the other end of the lead to the ground socket. If the indicator light on the phase comparator illuminates, it indicates that the corresponding phase is energized at high voltage. Phase comparison function: Insert the plug of the phase comparator into the display unit of the cabinet to be tested (e.g., L1, L2, or L3), and connect the other end of the lead to the display unit of another cabinet (also L1, L2, or L3). If the indicator light on the phase comparator illuminates, it means the two phases are not in phase; if the indicator light does not illuminate, it means the two phases are at the same potential and are in phase.
Outline Dimension Drawing (mm)
Previous
Next