Outdoor Pole-Mounted Fast Recloser

Automatic reclosers are intelligent switching devices used in distribution network automation. They are control switches that detect fault currents, interrupt the fault current within a specified time interval, and then reclose a predetermined number of times. When a short circuit occurs on the line, the recloser performs opening and closing operations in a prescribed sequence and at set time intervals. In the event of a permanent fault, after completing the predefined sequence of operations, if reclosing fails, the device locks in the open position to isolate the faulted section; once the fault is cleared, manual reset is required to unlock it. For transient faults, during the opening–closing cycle, if reclosing is unsuccessful, subsequent opening–closing operations are halted, and after a specified delay the device returns to its initial settings, ready to respond to the next fault. The recloser can execute multiple opening–closing cycles according to a preprogrammed sequence of operations.
Keywords:

Product Overview

Automatic reclosers are intelligent switching devices used in distribution network automation. They are control switches that detect fault currents, interrupt the fault current within a specified time interval, and then reclose a predetermined number of times. When a short circuit occurs on the line, the recloser performs opening and closing operations in a prescribed sequence and at set time intervals. In the event of a permanent fault, after completing the predefined sequence of operations, if reclosing fails, the device locks in the open position to isolate the faulted section; once the fault is cleared, manual reset is required to unlock it. For transient faults, during the opening–closing cycle, if reclosing is unsuccessful, subsequent opening–closing operations are halted, and after a specified delay the device returns to its initial settings, ready to respond to the next fault. The recloser can execute multiple opening–closing cycles according to a preprogrammed sequence of operations.


Terms of Use

Altitude not exceeding 2,000 meters; pollution severity level: Level IV.
Ambient air temperature: -45°C to +40°C; daily temperature range: 25°C.
Wind speed shall not exceed 35 m/s; seismic intensity shall not exceed Grade 8.
Areas free from flammable, explosive, or chemically corrosive hazards.


Implementation Standard

GB 11022-1999 “Common Technical Requirements for Standards of High-Voltage Switchgear and Control Equipment”

GB 311.1-1997 “Insulation Coordination for High-Voltage Transmission and Transformation Equipment”

GB 3309-1989 “Mechanical Tests of High-Voltage Switchgear at Ambient Temperature”

GB 25284-2010 “12 kV–40.5 kV High-Voltage AC Automatic Recloser”

GB 1208-2006 “Current Transformers”

GB/T 1984-2024 “High-Voltage AC Circuit Breakers”

GB/T 11022 “Common Technical Requirements for Standards of High-Voltage Switchgear and Control Equipment”

GB/T 7261-2000 “Basic Test Methods for Relays and Devices”

GB/T 20840.7-8 “Electronic Voltage/Current Transformers”

GB/T 4208 “Ingress Protection Rating (IP Code)”

DL/T 593 “Common Technical Requirements for High-Voltage Switchgear”

DL/T 721 “Remote Terminal Units for Distribution Automation”

DL/T 844-2003 “General Technical Specifications for 12 kV Maintenance-Reduced Outdoor Distribution Switchgear”

DL403-2000 “Technical Specifications for Ordering 12–40.5 kV High-Voltage Vacuum Circuit Breakers”

IEC 62271-111:2005


Technical Specifications

Project

Unit

Numerical value

Rated voltage

kilovolt

15.5

27

38

40.5

Rated frequency

Hertz

50/60

50/60

50/60

50/60

Rated current

A

630/800

630/800

630/800

630/1250

Rated short-circuit breaking current

kA

12.5/16

12.5/16

12.5/16

12.5/16

Rated short-circuit making current

kA

32.5/41.6

32.5/41.6

32.5/41.6

32.5/41.6

Rated short-circuit breaking current

kA

12.5/16

12.5/16

12.5/16

12.5/16

Rated short-circuit duration

s

3

3

3

3

Rated Operating Sequence

 

Open – 0.5 s – Close – 2 s – Close – 5 s – Close – Interlock

Mechanical life

times

10000

Rated short-circuit breaking current breaking operations

times

30

30

30

30

Power-frequency withstand voltage (1 minute): phase-to-phase, phase-to-ground / break contacts

kilovolt

50

70/85

90/115

95/118

Rated lightning impulse withstand voltage

kilovolt

110

135/155

176/200

185/215

Secondary withstand voltage (1 minute)

kilovolt

2

2 2 2

Protection Level

IP65

Main Mechanical Parameters

Project

Unit

Numerical value

Rated voltage

kv

15.5

27

38

40.5

Contact opening distance

mm

9±1

12±1

15±1

16±1

Average tripping speed

m/s

1.0±0.2

1.2±0.3

1.4±0.4

1.4±0.4

Average closing speed

m/s

0.6±0.2

0.8±0.3

0.9±0.4

0.9±0.4

Contact closing bounce time

m/s

≤ 3

≤ 3

≤ 3

≤ 4

Contact closing and opening are out of phase.

m/s

≤ 2

≤ 2

≤ 2

≤ 2

Overtravel

mm

3±0.5

3±0.5

3±0.5

3±0.5

Trip time

m/s

≤ 45

≤ 45

≤ 45

≤ 45

Closing time

m/s

≤ 60

≤ 60

≤ 100

≤ 100


External mounting dimensions