undefined
+
  • undefined

35kV grounding switch

The JN22-40.5/31.5 kV series indoor high-voltage earthing switch (hereinafter referred to as the “earthing switch”) is a new type of earthing switch developed by our company through the introduction of advanced foreign technologies and in response to market needs. It is suitable for use in indoor 3–40.5 kV three-phase AC power systems operating at 50 (60) Hz, and can be paired with various models of high-voltage switchgear. It may also be used for earthing purposes during maintenance and inspection of high-voltage electrical equipment. Comprehensive testing has demonstrated that its performance complies with the requirements of GB 1985 “AC High-Voltage Isolating Switches and Earthing Switches” and IEC 129.
Keywords:

Product Overview

The JN22-40.5/31.5 kV series indoor high-voltage earthing switch (hereinafter referred to as the “earthing switch”) is a new type of earthing switch developed by our company through the introduction of advanced foreign technologies and in response to market needs. It is suitable for use in indoor 3–40.5 kV three-phase AC power systems operating at 50 (60) Hz, and can be paired with various models of high-voltage switchgear. It may also be used for earthing purposes during maintenance and inspection of high-voltage electrical equipment. Comprehensive testing has demonstrated that its performance complies with the requirements of GB 1985 “AC High-Voltage Isolating Switches and Earthing Switches” and IEC 129.


Working conditions

● Applicable to the following environments

The elevation shall not exceed 1,000 meters;
Ambient temperature shall not exceed +40°C or fall below -10°C;
The daily average relative humidity shall not exceed 95%, and the monthly average shall not exceed 90%.
Seismic intensity does not exceed 8 degrees;
● Not applicable to the following venues
The installation location is subject to gases, vapors, chemical precipitates, dust and dirt, as well as explosive and corrosive substances that can severely impair the insulation and conductivity of the earthing switch; furthermore, the installation location experiences frequent and severe vibrations.


Implementation Standard

GB1985


Technical Specifications

Project

Unit

Data

Rated voltage

Kv

35

Maximum voltage

Kv

40.5

Thermal stability current

KA

31.5

Thermal stability current duration

S

4

Short-circuit making current

KA

80

Dynamic stability current

KA

80

Rated
Insulation
Level

Rated short-time power-frequency withstand voltage

Kv

Relatively and
Between phases

95

Rated lightning impulse withstand voltage

185