language
Sensor and Insulator Series
Install in locations free from fire hazards, explosion risks, and severe vibration.
Category:
24kV Insulator Series
Keywords:
Working conditions
● Ambient temperature: -45°C to +40°C
● Humidity: maximum daily average 95%, maximum monthly average 90%
● Altitude: not exceeding 1,000 meters
● Maximum daily average temperature: +35℃
● Maximum seismic intensity: Grade 8
● Install in locations free from fire hazards, explosion risks, and severe vibration.
Implementation Standard
GB311.1, GB/T7354, GB/T3906
Technical Specifications
| Rated voltage Ur Kv (effective) |
Rated short-time power-frequency withstand voltage Ud Kv (effective) |
Lightning impulse withstand voltage Up Kv (peak) |
Mechanical strength > N | Creepage distance (creepage ratio) 20 mm/kV > mm |
1.1 Ur/V3 voltage Partial discharge ≤ 3 pC |
| 3.6 | 25 | 40 | 10000 | 72 | 3 |
| 7.2 | 30 | 60 | 10000 | 144 | 3 |
| 12 | 42 | 75 | 10000 | 240 | 3 |
| 24 | 68 | 125 | 10000 | 480 | 3 |
| 40.5 | 95 | 185 | 10000 | 810 | 3 |
External dimensions (mm)
ZJ-24Q or CG11-24Q
|
TG1-24/218
|
TG2-24/310
|
TG3-24/330
|
CH2-24Q/165A
|
CH3-24Q/206A
|
Previous
Next