Contact box

The contact box is manufactured using the epoxy resin APG process and is suitable for indoor power systems with rated voltages of 35 kV and below. It is used in various handcart-type switchgear to provide insulation, isolation, and transitional connections.
Keywords:

Product Overview

The contact box is manufactured using the epoxy resin APG process and is suitable for indoor power systems with rated voltages of 35 kV and below. It is used in various handcart-type switchgear to provide insulation, isolation, and transitional connections.


Terms of Use

1. Application environment: indoor use, no dripping water, no risk of flammability or explosion, and no chemically corrosive gases.
2. Altitude (m): Not exceeding the standard value of ≤1000; when a specific altitude is specified, altitude correction shall be applied.

3. Ambient temperature (°C): Maximum temperature (24-hour average): +40°C; Minimum temperature: -25°C; Daily temperature range: <25 K

4. Humidity: Daily average relative humidity: ≤95%; monthly average relative humidity: ≤90%.

5. Relative humidity range requirement (%): ≤95%

6. Seismic Performance Requirements: Seismic Intensity: 8, Horizontal Ground Acceleration: 0.3g, Vertical Ground Acceleration: 0.15g

7. Contamination Level: Class II


Implementation Standard

GB311.1-2012
GB/T 4109-2022
GB/T 3906-2020
GB7354-2003
GB/T 5582-1993
GB/T 5169.16-2008
GB/T 11022-2020


Technical Specifications

Serial Number

Project

Unit

Standard parameter value

1

Rated voltage

KV

3.6 ~40.5

2

1-minute power-frequency withstand voltage (effective)

KV

Table 1

3

Rated lightning impulse voltage (peak)

4

Partial discharge quantity

PC

Table 2

5

Creepage distance to voltage

mm/kv

≥20

6

Clearance for Air Insulation

mm

≥125 (for 12 kV)

≥180 (for 24 kV)

≥300 (for 40.5 kV)

7

Flame-retardant rating

Subject to customer requirements.

8

Environmental Testing

High-temperature test

degrees Celsius

140 (24h)

9

Low-temperature test

degrees Celsius

-40 (24h)

10

Thermal cycling test

degrees Celsius

-40 to 125°C, 5 cycles, with a 2-hour interval


Test voltage

Rated voltage

Ur (kV)

System nominal voltage

Un (kV)

1-minute power-frequency withstand voltage RMS value Ud

Kv

RMS value of lightning impulse voltage Up

Kv

General Value

 

3.6

3

25

27

40

46

7.2

6

32

34

60

70

12

10

42

48

75

85

24

20

65

79

125

145

40.5

35

95

118

185

215


Partial discharge

Equipment rated voltage

Apply voltage

Kv

Partial Discharge Measurement Voltage

Kv

Allowable partial discharge quantity

PC

Your

1.3Ur

1.1Ur

≤3


Outline Dimension Drawing (mm)