undefined
+
  • undefined

Outdoor Prefabricated Substation (European Style)

The YB-K-12 series outdoor prefabricated substation (European style) is a compact indoor or outdoor distribution device pre-assembled at the factory, integrating high-voltage switchgear, distribution transformers, and low-voltage distribution equipment according to a specified wiring scheme. It organically combines functions such as high-voltage power reception, transformer transformation, and low-voltage distribution, all housed within a moisture-proof, rust-proof, dust-proof, rodent-proof, fire-resistant, theft-proof, insulated, fully enclosed, and mobile steel-structure or non-metallic enclosure, enabling fully enclosed, integrated electromechanical operation.
Keywords:

Product Overview

The YB-12 series outdoor prefabricated substation (European style) is a compact indoor/outdoor distribution device pre-assembled at the factory, integrating high-voltage switchgear, distribution transformers, and low-voltage distribution equipment according to a specified wiring scheme. It organically combines functions such as high-voltage incoming power reception, transformer transformation, and low-voltage distribution, all housed within a moisture-proof, rust-proof, dust-proof, rodent-proof, fire-resistant, theft-proof, insulated, fully enclosed, and mobile steel or non-metallic enclosure, enabling fully enclosed, integrated electromechanical operation.
Widely used in both indoor and outdoor settings, including urban power grid upgrades, residential communities, high-rise buildings, industrial and mining facilities, hotels, shopping malls, airports, railways, oilfields, ports, highways, and temporary power supply installations.


Terms of Use

● Altitude: ≤1000 m;
● Ambient temperature: upper limit +40°C, lower limit -25°C;
● Relative humidity: daily average not greater than 95%, monthly average not greater than 90%;
● Installation location: Areas free from fire hazards, explosion risks, conductive dust, corrosive chemical gases, and severe vibration;
● If the requirements for normal operating conditions cannot be met, users are requested to consult with our company to resolve the issue.


Implementation Standard

GB/T 17467-1998 “Prefabricated High-Voltage/Low-Voltage Substations” and DL/T 537-93 “Technical Specifications for Ordering 6–35 kV Box-Type Substations”


Functions and Features

● High-voltage switchgear, distribution transformers, low-voltage switchgear, electric energy metering equipment, and reactive power compensation devices are integrated according to a specified scheme, resulting in a highly complete and compact packaged solution.
● Comprehensive high- and low-voltage protection ensures safe and reliable operation with simple maintenance;
● Small footprint, low investment, short production cycle, and easy mobility;
● Flexible and versatile wiring options; unique structure: a distinctive honeycomb-style, double-layer (composite panel) enclosure that is robust, provides excellent thermal insulation while facilitating heat dissipation and ventilation, boasts an aesthetically pleasing appearance, and achieves a high degree of protection. Enclosure materials are available in stainless steel, titanium alloy, aluminum alloy, cold-rolled sheet, and color-coated steel sheet.
● Diverse models: available in universal, villa, compact, and other styles;
● The high-voltage ring main unit can be equipped with a feeder automation terminal (FTU) to achieve reliable detection of short-circuit and single-phase-to-ground faults, featuring “four-remote” functions that facilitate the upgrade to distribution network automation.


Technical Specifications

Technical Parameters of Load Switch

Project

Unit

FKN12-12 Load Switch

FZN12-12 Vacuum Load Switch

Rated voltage

kilovolt

10

Maximum operating voltage

KV

12

Rated frequency

Hertz

50

Rated current

A

630

Rated breaking load current

A

630

Thermal stability current (RMS)

kA/S

20/2

April 20

Dynamic stability current

kA

50

50

Short-circuit making current (peak)

kA

50

50

Number of full-load breaking operations

next time

20

10000

Mechanical life

next time

2000

10000

1-minute power-frequency withstand voltage (phase-to-phase and phase-to-ground)

kilovolt

42

42

Lightning Impulse Voltage (Phase-to-Phase and Phase-to-Ground)

KV

75

75

Technical Parameters of High-Voltage Fuses

Model

Rated Voltage (kV)

Breaking current (A)

Breaking current (kA)

Melt Rated Current (A)

British model

Domestic model

SDL*J

XRNT-12

12

40

31.5

6.3, 10, 16, 20, 25, 31.5, 40

SFL*J

XRNT-12

12

100

31.5

50, 63, 71, 80, 100

SKL*J

XRNT-12

12

125

31.5

125

Model

Trip unit type

Trip unit rated current

Switching capacity

DW15-630

Thermo-electromagnetic or electronic

315, 400, 630

40

DW15-1000

Thermo-electromagnetic or electronic

630, 800, 1000

50

DW15-1600

Thermo-electromagnetic or electronic

1600

50

DW15-2500

Thermo-electromagnetic or electronic

1600, 2000, 2500

60

CW1-2000

Intelligent

630, 800, 1000, 1250, 1600, 2000

65(80)

CW1-3200

Intelligent

2000, 2500, 3200

100


Substation Structural Diagram

 

Get a Quote

Through the previous introduction, we believe you have learned enough about us and are confident to cooperate with us. Please leave your information quickly, We will contact you within 24 hours!

Submit

Get a Quote

Through the previous introduction, we believe you have learned enough about us and are confident to cooperate with us. Please leave your information quickly, We will contact you within 24 hours

Submit