undefined
+
  • undefined

Indoor High-Voltage Vacuum Circuit Breaker

The VS1 (ZN63)-12 series indoor handcart-type high-voltage vacuum circuit breaker is a three-phase, 50 Hz, 12 kV rated indoor switchgear designed for the control and protection of industrial and mining enterprises, power plants, substations, and electrical installations, and is particularly suitable for applications involving frequent operation. It features an integrated operating mechanism and circuit-breaker body, allowing it to be configured either as a fixed installation unit or as a handcart unit when equipped with a dedicated pusher mechanism. The main circuit section can incorporate fully encapsulated pole assemblies, enabling miniaturization, high reliability, and maintenance-free operation. This product can be paired with KYN28A-12 (GZS) and other center-mounted handcart-type switchgear cabinets for fixed installations, or with XGN-series fixed switchgear cabinets for stationary applications.
Keywords:

Product Overview

The VS1 (ZN63)-12 series indoor handcart-type high-voltage vacuum circuit breaker is a three-phase, 50 Hz, 12 kV rated indoor switchgear designed for the control and protection of industrial and mining enterprises, power plants, substations, and electrical installations, and is particularly suitable for applications involving frequent operation. It features an integrated operating mechanism and circuit-breaker body, allowing it to be configured either as a fixed installation unit or as a handcart unit when equipped with a dedicated pusher mechanism. The main circuit section can incorporate fully encapsulated pole assemblies, enabling miniaturization, high reliability, and maintenance-free operation. This product can be paired with KYN28A-12 (GZS) and other center-mounted handcart-type switchgear cabinets for fixed installations, or with XGN-series fixed switchgear cabinets for stationary applications.


Terms of Use

Altitude not exceeding 2,000 meters;
Ambient temperature: maximum +40°C; minimum -15°C
Ambient humidity: daily average relative humidity ≤95%; monthly average relative humidity ≤90%.
Seismic intensity: below magnitude 8
Use in locations where there is no standing water, no risk of fire or explosion, no severe contamination, no chemical corrosion, and no severe vibration.


Technical Specifications

Project

Unit

Parameters

Rated voltage

kilovolt

12

Maximum operating voltage

kilovolt

12

Rated current

A

630 1250

630 1250 1600 2000 2500 3150

1250 1600 2000 2500 3150 4000

Rated short-circuit breaking current (rated thermal withstand current—RMS value)

kA

20/25

31.5

40

Rated dynamic stability current (peak)

kA

50/63

80

100

Rated Insulation Withstand Current (Rated Dynamic Stability Current—Peak Value)

kA

50/63

80

100

4S rated short-circuit withstand current

kA

20/25

31.5

40

Rated Insulation Level

Withstand voltage during operation (before and after rated breaking) / 1 min power-frequency withstand voltage

kilovolt

To ground 42 (fracture 48)

Impact and voltage withstand (before and after rated breaking) / Peak rated lightning impulse withstand voltage

kilovolt

To ground: 75 (fracture: 85)

Rated thermal stability time

s

4

Rated Operating Sequence

 

Break - 0.3 s - Close-break - 180 s - Close-break

Mechanical life

time

20000

Rated short-circuit breaking current breaking operations

time

50

Rated closing voltage of the operating mechanism (DC)

V

AC, DC 110, 220

Rated Trip Voltage of the Operating Mechanism (DC)

V

AC, DC 110, 220

Contact opening distance

mm

11±1

Overtravel (contact spring compression length)

mm

3.5±0.5

Three-phase opening and closing bounce time

milliseconds

≤2

Contact closing bounce time

milliseconds

≤2

Average tripping speed

m/s

0.9~1.2

Average closing speed

m/s

0.5~0.8

Trip time

At the maximum operating voltage

S

≤0.05

At the minimum operating voltage

S

≤0.08

Closing time

S

0.1

Main circuit resistance of each phase

microohm

630 ≤50

1250 ≤45

Allowable cumulative wear thickness of moving and stationary contacts

mm

3


External mounting dimensions